DUV 14
The DUV 14 signal monitor is intended for use in conjunction with analog or digital UV sensors of various designs for monitoring UV radiation sources. Integration of temperature and flow sensors, as well as dose output is also possible.
Data sheets and information
General Attributes
The UV Monitor DUV 14 in combination with UV probes of different configurations is intended for direct display and monitoring of the irradiance of UV radiation sources, in particular for UV disinfection systems. The monitor meets the requirements of drinking water disinfection according to DVGW worksheet W294-3 or ÖNORM M5873. Next to the monitoring of the irradiance of UV radiation sources the monitor can also be used for logging other important variables like temperature, flow rate and air pressure and for calculating an irradiation dose.
TECHNICAL DATA
| Parameter | Value |
|---|---|
| Mass | Ca. 500 g |
| Dimensions (W x H x D) | 96 mm x 96 mm x 64 mm |
| Installation dimensions (W x H x D) | 92+0,8 mm x 92+0,8 mm according to DIN 43700, mounting depth min. 75 mm |
| Display | alphanumeric LCD-Display (double-spaced, multi-coloured) |
| Supply voltage | 90…264 V AC (50-60 Hz) / 100…300 V DC |
| Power input | 2,5 W |
| Inlets | 1 analogue input for connection of UV photodiodes; 1 analogue input for UV-sensor with voltage output 0…2/5/10 V DC; 1 analogue input for sensor with voltage output 0…2 V DC; 2 analogue inputs for sensors with current output 0/4-20 mA; 1 pulse input for flowmeter; 1 floating pulse input 115…230 V AC for switch-on-cycles counter |
| Outlets | 1 analogue output 0/4-20 mA DC; outputs for 2 voltage sensors and 2 current sensors each; 1 relay output for main alarm; 1 relay output for pre-alarm; 1 relay output for temperature alarm |
| Interfaces | 1 RS485 interface |
| Degree of protection | IP65 (Front panel in mounted state) |
| Working temperature range | 0 … 40 °C |
| Environmental conditions | Relative humidity < 90 % (no condensation or corrosive atmosphere) |